Mechanical and Plumbing BoardFeb. 27, 2024

Recommendation 20240227-006 Parking Garage Exhaust Recommendation — original pdf

Recommendation
Thumbnail of the first page of the PDF
Page 1 of 1 page

MECHANICAL AND PLUMBING BOARD RECOMMENDATION 20240227-6 Seconded By: Joe Cooper Date: February 27, 2024 Subject: Parking Garage Exhaust Ventilation Motioned By: Bill Harris Recommendation Board has made a recommendation to identify parking garage exhaust as class 2 environmental exhaust in keeping align with ASHRAE and other recognized standards. Description of Recommendation to Council Environmental Class 1 and Class 2 air duct exhaust shall terminate no less than 3 ft from a property line, 10 ft above a public way, 3 ft from openings into the building and the minimum separation distance from ventilation system outdoor air intakes determined in accordance with Section 402.4.1 Rationale: For the purpose of maintaining consistency with the 2024 Uniform Mechanical Code and ASHRAE Standards. Vote 7-0 For: Robert Thornton, Joe Bowie Bobbi Jo Foster, William Harris, Joseph Cooper, Stephen Cox, and Ramon Perez Against: None Abstain: None Absent: Kyle Smith, Blaine Butler, Mark Mapes and Alex Ramires Attest: 1 of 1