15.2 - 1006 Shelley Ave - Structural Engineer's Report — original pdf

Backup
Thumbnail of the first page of the PDF
Page 1 of 16 pages

TUCKER ■■■ eng1neenng Tucker Engineering, Inc. Erin Dunnigan 1311 Chisholm Trail, Ste 303 Round Rock, Texas 78681 Registration F-8611 Reference Number 43070 Issued May 22, 2026 Inspected May 19, 2026 1006 Shelley Avenue Austin, Texas 78703 Structural Inspection Report Type of Structure This is a two-story, wood frame, single family house with horizontally lapped siding around the exterior. The foundation is a pier and beam on cedar trunks. The roof structure is conventionally framed in gable and hip configurations and is covered with asphalt shingles. The lot is fairly level. Observations Foundation The pier and beam foundation/ floor system was constructed with 2x10 joists at 24 inches on-center, spanning front to rear underneath the main rooms. The central hallway is supported by 2x6 joists, spanning left to right. The joists were supported by 4x6 beams which were themselves supported by a combination of cedar tree trunks and grouted cinderblock piers located at roughly 5-foot on-center. The components of the foundation were generally in good condition. There was a dry-stacked cinderblock pier at the front-right corner of the porch which was precariously stacked. Damages were observed around the house as follows: 1. Interior a. Foyer i. A 1/32-inch sheetrock crack above the opening to the office. 1 Authenlisign ID: 18A662F5-075A-F111-8FCA-002248359474 b. Office i. The door is out of plumb. ii. Multiple hairline sheet rock cracks in the ceiling. Measurements were taken inside the house as shown in the enclosed diagram. It was determined that the foundation had significant humps and dips throughout. Cross sections of the foundation were analyzed as shown in the enclosed diagrams. The utility was origina lly constructed as exterior space with a slope built into the floor and was excluded from the elevation readings. The soil on this lot was expansive clay. Drainage The drainage patterns around the house appeared to be satisfactory. Superstructure No excessive movements, deflections or any other evidence which would indicate a structural problem with the roof or wall framing of this house were observed. Conclusions and Recommendations Foundation The foundation has experienced movements with deflections and damages as previously described. The magnitudes of the deformations are somewhat beyond allowable tolerances. However, the foundation is structurally intact and the house is safe and livable. The beams and floor systems may be lifted off the existing piers and fixed in a more level position. I recommend that the dry-stacked cinderblock pier be replaced with a new spread footing constructed as shown in the enclosed details. I also recommend that the beams be positively anchored to the grouted cinderblock piers as shown in the enclosed details. The central Texas area has clay soil, which shrinks and swells with variations in t he moisture content. This phenomenon can cause foundations to move and cracks to occur. Periodic adjustments will be necessary to maintain a level condition. Aulhenlislgn ID' 16A662F5-075A-F111-BFCA-002248359474 The cedar tree trunk piers have been supporting the structure for over 100 years and still appear to be in generally good condition. However, they will continue to rot from the bottom and slowly sink into the ground. The cedar trunks should be inspected periodically and reinforced with new concrete footings as necessary. Drainage No remedial work necessary. It was dry during the time of the inspection and pooling of water and/or flow of water, which is not apparent at this time, may occur during heavy rains. Superstructure No remedial work necessary. I certify that I (or my representative) made this inspection and have no interest, present or prospective, in this property or anyone involved with this property. I warrant that I (or my representative) visually inspected the components of this property as addressed in this report in a diligent manner and have honestly reported the findings of existing conditions and have made recommendations based on my experience and opinion. Neither Tucker Engineering nor I express or imply any guarantee of specific future structural performance with the limited scope of this inspection; rather, this is my best effort to interpret my observations and develop an opinion as to structural significance. There may be rotten or termite damaged wood that is not visible without destructive investigation. The conditions of the various components of this property described in this report are true as of the date of inspection. Changes may occur in this property after the inspection date, which could make null and void the contents of this report. No other warranty, either expressed or implied, is hereby made. Structural Engineer , P.E. i r I Authentisign ID: 18A662F5-075A-F111-8FCA-002248359474 REAR /1., 1 0 SPOT ELEVATION MEASUREMENT {IN.) DIRECTION OF WALL LEAN PROPOSED PIER OR PILE LOCATION EXISTING PIER OR PILE LOCATION TIii$ p 1./\N IS DELIVERED IN CONJUNCTION WITH A WRI TTEN REPORT AND IS INCOMPLETE WITHOUT IT. READI NGS HAVE BEEN ADJUSTED FOR FLOOR COVE R. GARAGE READINGS TAKEN ON CEILING ELEV ATION READINGS WERE TAKEN 0511912026. PATIO SLAB ~3.9" 3.2"6; l 25"~ 4.5" .._ ... 3.9" SECTION 1 PAGE 2 ~16" r rn -n -, - - - 34" i\j I 4.2"/lli, :,., - n -,4.2" 4.3"~ - r I l9 c2 4.2"~ 1' I 5' iS I_ ~4.4" ~2.9" ~ 3" ~4.1" ~3.2" 4.7" ~ 4.9",;; 3.6"~ ~2.9" 4,1"~1 il93.8" -,3.3" 4.3"~ 0 UJ ~ , N (.9 - r- <( ~ CL Vl FRONT TUCKER 1 1006 Shelley Ave, Austin, TX 7 ■■■ engmeenng I Elevat,onReadtngs Page: 1 Scale: l /811 = 1'-0" Oat Issued: 5/21/2026 Tucker Engineering, Inc. - F-8611 - 1311 Chisholm Tratl, Ste 303, Round Rock, Texas 78681 - TuckerEngineering.net (512) 255-7477 Aumen11s1gn 10. 16A002r:;.o75A·F111·8FCA•002240350474 / THEORETICAL UNI FORM SLOPE FOUNDATION SURFACE - ~16" l > ~ 3.4" I ~ 4.2" ' 0.9" J >, 35' t 4.3· I t (0----fc~,~t~' ?,~:ION CROSS SECTION NOTES: MEASURED UNIFORM SLOPE: 2.7" 4.2" ALLOWABLE UNIFORM SLOPE (1%): MEASURED BENDING DEFLECTION: 0.9" ALLOWABLE BENDING DEFLECTION (L/360): 1.2" FOUNDATION SURFACE """ THEORETICAL UNIFORM SLOPE (\;41" / v\!...-__ __.. ____ .....,.., ; . . .__ - - - -..... ,~;<.:.-- - 613.4" ' ~49" ~ 5"/ 1 __ 33' 1.0" r J ~4.5" l ( 2 ~ ~'~t~· ?,~:ION CROSS SECTION NOTES: MEASURED UNIFORM SLOPE: 0.4" 4.0" ALLOWABLE UNIFORM SLOPE (1%): MEASURED BENDING DEFLECTION: 1.0 ALLOWABLE BENDING DEFLECTION (L/360): 1.1" II /~~~{]ff;~,111 \ • 1 ; * / "- 1 {~/. ................... :· ... "'..~ ~ ~ MATTHEW SOLUM -,_ ........ ....... ............ : .. ·~ 1t ~··. /r.... J 129 /77 .·<Z;", f ~·· '• v;;•.9crns~~···'# .:' TUCKER ■■■ engmeenng . 1006 Shelley Ave, Austin, TX 78703 ,,,{ss10NA°t.t~~.:- Foundatlon Cross Sections ~;....c::~u."-''-i,.:o.:"?-::'--~---- Page: 2 Scale: 1/8""' 1'-0" Dater -ued: 5/21/2026 Tucker Engineering, Inc.• r•8611 • 1311 Chisholm Trail, Ste 303, Round Rock, Texas 78681 TuckerEngineering.net • (512) 255·7477 Authenlisign ID: 18A662F5--075A-F111-8FCA-002248359474 16 GA. STEEL STRAP ---. 12" (i1 PIER SHAFT #3 TIES AT 24" O.C. ~ BEAM, PER PLAN (4) #4 VERTICAL BARS VARIES, 3' MAX. 2'X2' SPREAD FOOTING 1' .... (3) #4 BARS EACH WAY IN BOTTOM OF PIER -- - - - ....-----1·. I 2' 1 ( l ,)· SPREAD FOOTING/ _EJ_ER DETAl!::_ - -~ SCALE: NOT TO SCALE NOTES: THESE PIERS IN CLAY SOIL MAY EXPERIENCE MOVEMENT DUE TO MOISTURE CHANGES RESULTING IN CRACKS AND STICKING DOORS. ADJUSTMENTS MAY NEED TO BE MADE PERIODICALLY. EXISTING BEAM SIMPSON CS16 16-GAUGE STEEL FLAT-STRAP / - FASTEN TO BEAM WITH (3) #10 TAPCON SCREWS INTO EACH SIDE OF PIER (TYP.) EXISTING CMU PIER _ ........... ,,,, - - - 1, t. 0 F T [ ,, / ~\~·:~~··1'1/\, ,, .... ~ ··.*' t.~J .................... :-:!'..~ ~ t ..... : ·.' ................. / .. } t1 .-o·•.. 129777 _.:~ ~ TUCKER 1006 Shelley Ave, Austin, T¥a:O~;r.{sX6~1t"~,-<>3/ ------ - ---- -- - - --- ~ MATTHEW SOLUM ---..) RETROFIT STRAP DETAIL ../ SCALE: NOT TO SCALE 2 NOTES: ( ■■■engineering Supplemental Details page: 3 Sca le: 1/8" = 1'-0" Date sued: 5/21/2026 ..... -zz~u'-".,,,.~"-=➔cw-4----- Tucker Engineering, Inc.· F-8611 • 1311 Chisholm Trail, Ste 303, Round Rock, Texas 78681 • TuckerEngineering.net • (512) 255-7477 Authentisign ID: 18A662F5-075A-F111-8FCA-002248359474 1006 Shelley- Bat Foundation Quote for Repairs Recommended by Engineer Aulh&nl1$1gn ID: 18A662F5.(175A~F111·8FCA.002248359474 Bats Foundation Repair www.batsfoundationrepair.com1 (512) 584-6557 18414 N Heatherwilde Blvd (512) 584-6557 Pflugerville , Texas 78660 Date 05-23-2026 Site Address 1006 Shelley Avenue, Austin, TX 78703 Sales Representative Calvin Burnett ca!vin@ba1sfoundationrepair.com Quantity 1,736.66 sq ft Subtotal Total Client Details Erin Dunnigan (512) 919-0653 erin@teamprjce com 1006 Shelley Avenue Austin, , TX 78703 Product List Description Reshim Charge Engineered Block & Pad Engineer Certification Engineer Certific'llion Payment Deposit Balance Payment Terms: Payment Upon Completion FOUt -· . . -11'1 REPAIR Amount $7,597.89 $375.00 $695.00 $8,687.89 $8,667.89 $4,333.94 $4,333.95 Authentislgn ID: 18A662F5-075A-F111-8FCA-002248359474 • This proposal may be withdrawn by Bats Foundation Repairs, LLC If not accepted within thirty (30) days of the above date. • Customer is aware that proper maintenance, Gutters and Drainage, is required through the life of the structure. Customer understands and agrees that Bats Foundation Repair, LLC shall not be responsible for any damage caused by any lack of proper maintenance on the premises. • Bats Foundation Repair has inspected the structure and determined the scope of repairs based on the structure being built to code. We are not responsible for structures that are not built to code. • Customer understands final payment Is paid to foreman with check or cash. If paying with credit card an additional 3% will be added and payment will be taken over the phone with the office. Engineer Report (If Included) will be provided to client after final payment has been received. Additional Information Did you add the Engineer Certification product? Type of Foundation: Pier and Beam - Reshim Yes Yes Reshim comes with a one year warranty for adjustments. Warranty is transferable. See warranty obligations. Erin Dunnigan 1006 Shelley Avenue Austin, TX, 78703 erin@teamprice.com (512) 919-0653 May 23, 2026 FOUNDATION REPAIR Based on Tucker Engineering Report Legend .:~ Engineered Block & Pad I Reshim Charge Use straps to attach any existing blocks to beams 0 Slab -3.2 -2.0 cess Electric 0.4 0.0 Bath 2.8 -1.0 0.5 Kitchen 1.2 0.9 0.1 0.7 1.5 1.1 i -0.9 CK] 0 Access -0.2 1.3 0.6 1.1 1.4 Two Story Stucco Siding 3-4 Feet of Crawlspace Cedar Post/Cinder Block/Sonotube 4x6 Beams 0 Additional Joist replacement charged at $35/foot if needed Additional Beam replacement charged at $40/foot if needed Sonotube Pier $650 each if needed Engineered Block and Pad $375 each if needed Reshlm Charge 1,736.66 sq ft • ] #SEQ# Engineered Block & Pad Authentisign lu: 18 ;. A662F5-075 - A F111-8FCA-002248359474 1 • 1 1 - 2 1 - 3 1 - 4 1 - 5 1 - 6 1 - 7 1 - 8 1 - 9 Authentisign ID: 18A662F5-075A-F11 HlFCA-002248359474 1 • 10 1 - 11 1 • 12 1 • 13 1 • 14 1 • 15 1 • 16 1 - 17 1 • 18 Aulhentisign 10: 18A662FS-075A-F111-8FCA--002248359474 1 - 19 1 - 20 1 - 21 1 - 22 1 - 23 1 - 24 1 - 25 1 - 26 1 - 27 Authentisign ID: 18A662F5-075A-F111-8FCA-002248359474 1 - 28 1 - 29 1 - 30 1 - 31 1 - 32 1 - 33 1 - 34 1 - 35 1 - 36 Authentisign ID: 18A662F5-075A-F111-8FCA-002248359474 . 1 • 37 1 - 38 1 • 39 1 • 40 1 • 41 1 - 42 1 - 43 1 • 44 1 • 45 Authentisign ID: 18A662F5-075A-F111-8FCA-002248359474 1 - 46 1 - 47 1 - 48 1 - 49 1 - 50 1 - 51 1 - 52 1 - 53 1 - 54